Rotronic HF3A Humidity and Temperature Transmitter

WhatsApp for Price

 

  • Versatile design to meet diverse application needs​
  • Precise relative humidity and temperature measurement with additional psychometric calculations
  • Freely programmable outputs and scaling via NFC-Interface, including NFC powerless support
Category: Brand:

Description

The HygroFlex3 Advanced series is ideal for all applications where good accuracy measurement of humidity and temperature is of critical importance. The transmitters is designed for fixed installation and is suitable for HVAC and light industrial application.​

Specification

General Description
Device type Humidity and Temperature Transmitter
Range of application 0…100%rh (non-condensing)-10…60 °C with display-40…85 °C without display
Mounting type Wall, Cable (2m), Duct
Circuit type 2-wire: HF3A-23-/4-wire: HF3A-3 & HF3A-D
Psychometric Calculation Dew point (DP)Frost point (FP)Wet bulb temperature (Tw)Enthalpy (H)Vapor concentration (Dv)Specific Moisture (Q)Mixing ratio (R)Vapor concentration at saturation (Dvs)Vapor partial pressure (E)Vapor saturation pressure (Ew)Volume mixing ratio
Digital Interface Description
Interface Via NFC and USB
RS485 Half duplex, baud rate adjustable (only digital version)
Software compatibility HygroSoft Software
Protocol Description
Modbus RTU RS485 Interface (only digital version)
Power supply and connections Description
Supply voltage HF3A-2:  10…28 VDCHF3A-3/D: 18…36 VDC
Current consumption HF3A-2: 2×23 mAHF3A-3/D: < 50mA
Polarity protection Yes
Humidity Measurement Description
Sensor ROTRONIC Hygromer ® HT-1
Measurement Range 0…100%rh
Accuracy @23°C ± 1.2%rh
Repeatability ± 0.5%rh
Long Term Stability <1 %rh / year
Sensor Response Time Typically 10 sec, for 63 % of 35 to 80 %rh step change (1 m/s wind speed at sensor)
Temperature Measurement Description
Temperature Pt100 1/3 class B
Measurement Range Wall1 -10…60 °C (with display), -40…85 °C (without display)
Duct2 / Cable: -50…100°C
Accuracy @23°C ± 0.1 °C
Repeatability ± 0.05 °C
Long Term Stability <0.1 °C / year
Sensor Response Time Typically 4 sec, for 63 %rH of a step change (1 m/s wind speed at sensor)
Analog Output Description
Quantity 2
Assignment Outputs can be freely assigned to each measured temperature value.
Default setting assignment Output 1 = HumidityOutput 2 = Temperature
Standard Ranges HF3A-2: 4…20 mA
HF3A-3 / HF3A-D: 0…20 / 4…20 mA   0…1 /0…5 / 0…10 V
Default setting Ranges 4…20 mA
Measuring signal Freely scalable
Accuracy @ 23 °C Current output: ± 20 µAVoltage output: ± 1/5/10 mV
Measurement Interval 1 s
Short-circuit protection Yes
Load compensation HF3A-2: Automatically
HF3A-3 / HF3A-D: Configurable
Load resistance max. current output: 0 to 500 Ωmin. voltage output: 1 kΩ/ per volt scaling
Resolution 15 bit
Self-heating HF3A-2: max. 0.2 °CHF3A-3/D: max. 0.1 °C
Alarms Description
Assignment Alarms can be assigned to any measured value
Alarm thresholds High-Alarm, Upper Alarm thresholdLow-Alarm, Lowest Alarm threshold
Hysteresis For Low-Alarm and High-Alarm
Alarm indication on display All Alarms
Alarm trigger Low- or High-Alarm
Housing Specifications Description
Dimensions Cable:   122 x 82 x 40.5 mm (Housing), 144 x 15 mm (Probe)Wall:     122x172x40.5mm (Housing + Probe)Duct:    122x82x265.5mm (Housing + Probe)
Weight Wall:     204gDuct:    226gCablle:  332g
Housing material PC-ABS
IP protection IP653
Cable Connections 1x M12, screw terminals (2 x M12 for HF3A-D)
Conformity with standards Description
EMC directives EMC-Directive 2014/30/EU:
EN 61000-6-1EN 61000-6-2EN 61000-6-3EN 61000-6-4EN 61326-1
Soldering material Lead free (RoHS-Directive 2011/65/EU)
Fire protection class Housing material UL94-HBCable gland UL94-V2
FDA/GAMP directives GAMP5

The measurement range for the wall-mount unit is limited due to the proximity of the probe to the transmitter electronics.

The full measurement range of the duct mount unit can only be utilized if the transmitter electronics operate within the given application range.

IP65 is only fulfilled, when the necessary number of conductors is used so that the M12 cable strain provides an effective seal

Datasheet

HF3A